Network Setup
The BACnet setup screen is enabled by pushing position 1 switch (labeled
MAC) to the on (right) position. After conguration the switch must be
moved to the off (left) position.
The Network Setup screen gives the option for the user to congure the
Network and other parameters which have to be read from the network.
BACnet conguration requires the user to congure the following param-
eters.
1. Baud Rate - User can select any one of the 4 standard Baud rates for
RS485 communication from 9600, 19200, 38400 and 76800 by using the
change button. Auto baud features is not supported.
2. MAC Address - User can enter Medium Access Control address specic
to this device by touching on this eld. User can enter a value from 0 to
127 as this unit is a BACnet master, address 128 to 254 reserved for 254
and 255 reserved for Broadcast.
3. Device Instance - The Device instance number must be unique within a
BACnet internetwork to identify each device. Instance numbers are dened
as 22 bit long, in decimal instance number ranges from 0 to 4194,3,03.
FFFFNDD is the network addressing scheme, here FFFF represents the Fa-
cility code. N is the number of the network in the building and DD ranges
from 0 to 99 to represent the individual device on the network.
Five position dip
switch location