9
3.0 ELECTRICAL INSTALLATION
To access the electrical connections, turn the screws on the top of the case counter clockwise until the hinged cover
can be ipped up. The screws are captured and secured in the cover. Wiring is through the 1/2” conduit openings
and PG ttings in the case of remote sensors with cable option. Both current and voltage outputs are reverse wiring
protected.
Note: The Zero terminals, connected to digital output, provide a contact closure relay for automatic reset to zero pres-
sure by the monitoring system. CAUTION: ZERO input is for dry contact, do no apply voltage to ZERO Terminals
3.1 Electrical Termination
Wiring: 2-Wire - 4 to 20 mA (Current Output) and Remote Zero
Model 231RS when congured as a current output transducer is a true 2-wire, 4-20 mA current output device and
delivers rated current into any external load of 0-250 ohms.
When congured as a 4-20 mA current output device the current ow is in one direction only.
PLEASE OBSERVE POLARITY. WARNING: Damage may result on the unit if AC power is applied when the output
switch is congured in position A (4-20).
We suggest that an electrical cable shield be connected to the systems loop circuit ground to improve electrical noise
isolation.
Min. Supply Voltage: 15 + .02 x (Resistance of receiver plus line)
Max. Supply Voltage: 30 + .004 x (Resistance of receiver plus line)
The optional remote zero is a normally open relay wired between COM and REMOTE ZERO terminals. In order to initi-
ate ZERO function the relay contact should be closed and sensor must be vented to atmosphere.
Figure 4