3.3 Remote Sensors Installation
Conduit Version (P/N: 231GRSX3MX)
For conduit version remote sensors, use the following instructions:
1. Install the remote sensors into the system plumbing (use 3/4” hex to tighten”)
Important:
Each remote sensor is labeled “HIGH PRESSURE SENSOR or “LOW PRESSURE SENSOR”, respectively. Match up
the high pressure sensor to the high “HI (+)” pressure electrical terminals, and the low “LO (-)” pressure
sensor to the low pressure electrical terminals. Otherwise, the performance may not meet the product
linearity specications.
2. Install a 1/2” conduit tting into the remote sensor top cover and fasten the retaining nut.
3. Feed wires from a exible conduit through the remote sensor top, cover fasten the wires to terminals.
4. Screw on the top cover.
5. Fit conduit into conduit tting, and tighten conduit watertight strain relief.
To connect the wires from the remote sensor to the unit, remove the terminal blocks from the circuit board and use
the following chart:
Installation of the Model 231RS is now complete.
Chart 1. Electrical wiring chart for High &
Low Pressure Sensors (Conduit version)
CAUTION:
Reverse excitation will permanently
damage unit. Please follow wiring
instructions carefully.
Figure 6
Dimensional Drawing