4.1 Voltage Output Zero Adjustment
While monitoring the voltage between the positive output (+OUT) and common
(COM), and with the pressure port open to atmosphere, or with zero pressure
applied, the zero may be adjusted by turning the zero potentiometer screw.
For the 5 VDC Full Scale Output, the tolerance on zero and span settings is
±25mV. For the 10 VDC Full Scale Output, the tolerance on zero and span
settings is ±50mV. For absolute pressure ranges, the zero should be adjusted
with a full vacuum applied. See the chart below for nominal installed output at
atmospheric pressure for compound pressure ranges.
Diagram 5
NOMINAL “INSTALLED” OUTPUT AT ATMOSPHERIC PRESSURE
PSI 5 VDC Full Scale Outputs 10 VDC Full Scale Outputs
Compound 0.2 to 5.2 0 to 5 VDC 0.2 to 10.2 0 to 10 VDC
Range Voltage (VDC) Voltage (VDC) Voltage (VDC) Voltage (VDC)
(Factory Set to within ±25mV) (Factory Set to within ±50mV)
-14.7 to 25 2.051 1.851 3.903 3.703
-14.7 to 50 1.336 1.136 2.472 2.272
-14.7 to 100 0.841 0.641 1.482 1.282
-14.7 to 250 0.478 0.278 0.755 0.555
-14.7 to 500 0.343 0.143 0.486 0.286
-14.7 to 1000 0.272 0.072 0.345 0.145
-14.7 to 3000 0.224 0.024 0.249 0.049
Bar 5 VDC Full Scale Outputs 10 VDC Full Scale Outputs
Compound 0.2 to 5.2 0 to 5 VDC 0.2 to 10.2 0 to 10 VDC
Range Voltage (VDC) Voltage (VDC) Voltage (VDC) Voltage (VDC)
(Factory Set to within ±25mV) (Factory Set to within ±50mV)
-1 to 1.7 2.052 1.851 3.904 3.704
-1 to 3.4 1.336 1.136 2.473 2.273
-1 to 7 0.825 0.625 1.450 1.250
-1 to 17 2.494 0.278 0.756 0.556
- 1 to 35 0.339 0.139 0.478 0.278
-1 to 70 0.270 0.070 0.341 0.141
-1 to 200 0.225 0.025 0.250 0.050
5